Fire Exhaust Valve 200Ø

Indent 3-5 Days

Code

FDV200

Brand

RRP

$543.00

Minimum quantity

1

$472.18

Description

Fire Exhaust Valve 200Ø 

Kit Includes:
Fire Exhaust Valve (Grille)
Installation Frame/Ring LF
Installation Collar IC

MATERIAL AND FINISHING
Collar: Steel Epoxy painted
Central Cone: Steel Epoxy painted
Frame gasket: Polyurethane
Fireproof gasket: Silicate
Installation frame: Galvanised steel
Melting fuse: Brass

The Halton FDV is a circular fire valve, which combines a exhaust valve and fire damper for circular ducts. FDV prevents fire and smoke from spreading in ventilation ducts.

Operation as an exhaust valve – normal mode: The valve throttles the exhaust air flow and attenuates the duct noise. The pressure drop is dependent on the position of the central cone. The desired exhaust rate is set during the balancing of the air flows in a ductwork system.

Operation as a fire damper – emergency mode: The fire damper contains an integral thermal fuse. This fuse responds to a rise in temperature, which causes a spring-return central cone to close.

The thermal fuse is released at 50°C, 72°C, or 100°C.

APPROVAL
Fire tested to BS 476:part 22: 1987 by the Loss Prevention Council, the subject of FIRTO Technical Evaluation No. TE 6643. Complies with the Australian & NZ Building codes as an alternative solution (incorporating AS1682 as a guide line).

Verification as follows:
BRANZ Assessment FAR2687 dated 15 March 2006,
BRANZ Fire Resistance Test FP2376 dated 31 July 1997,
BRANZ Assessment FAR3668 dated 18 February 2011,
BRANZ Assessment FAR 97/1026 dated 10.01.1997.

The results of test No. FP2376 confirm the plasterboard mounting system for the FRH will satisfy AS1530.4-1990 for 120 minutes.